Specializing in the sales, service and installation of petroleum equipment |
| Overfill protection Audible |
||||||||||
![]() MR922-0500AA |
MORRISON BROTHERS 922 SERIES |
MODEL |
DESCRIPTION |
DOCS Features Install/Ops |
Inquiries? Call us 8am-5pm Pacific time, or email us. |
|||||
![]() Model 4517 |
OIL EQUIPMENT MFG 'KING' FILL ALARM |
MODEL |
DESCRIPTION |
DOCS Features |
||||||
| (*) Standard stem length is 5 1/4".
Models 4516 (9 3/4"stem length), 4518 (16 3/4" stem length) and 4519 (21 7/8" stem length) are recommended for larger and underground tanks. |
||||||||||
![]() PNLC1002 |
PNEUMERCATOR LC1000 SERIES
Offers up to four channels for audible (85db minimum) and visual (red light) notification of incidents such as high or low level, leak indication). Supplied with reset button to silence alarm and a button to test the alarm circuits. Includes one dry switch contact per channel (SPDT, rated 3 amps @ 120v, selectable as either normally open or normally closed). Uses up to 5000' of 2 conductor 18AWG cable. Housed in NEMA 4 weatherproof enclosure. |
MODEL |
DESCRIPTION |
DOCS Features Install/Ops |
||||||
![]() PNLS600-B12 |
PNEUMERCATOR SENSORS/PROBES
For use with LC1000 series. LS600 level switches: Available in two different configurations with one to four actuation points. Model LS600 includes a die cast aluminum housing, NEMA 4 rated with a 1/2" conduit fitting. Model LS600A does not have the housing or conduit fitting. Choose between brass or stainless steel shafts with stainless steel floats. |
MODEL |
DESCRIPTION |
|||||||
Mechanical |
||||||||||
MR9095A |
MORRISON MODEL 9095A VALVE — •Overfill prevention valve installed at the fill port of an aboveground tank. •Available in 2" and 3". It is imperative to note that the 2" valves requires a 4" tank opening for installation, and that the 3" valve requires a 6" tank opening. •Terminates flow of product into the tank when the liquid level reaches a pre-set shutoff point (typically 90% to 95% of tank capacity). Allows full flow of product up to within one to two seconds of the valve's closing. Cushioned shutoff prevents abrupt kickback or jolt in the line. •The 2" valve is normally used on above- ground tanks utilizing 'top fill', or making the fill connection at the top of the tank. The 3" valve, meanwhile, is used in 'low fill' or remote fill applications, where the fill connection is at ground level and piping carries product to the top of the tank in the fueling process. •Requires tight delivery connection when using. Many 9095A valves are supplied with camlock fitting at hose connection end. Mascott stocks the models with male camlock adapter ends. Dust cap must be ordered separately. |
MODEL |
DESCRIPTION Valve, overfill, 3" FPT x 6" |
DOCS Features 9095A 9895A aviat Install/Ops 9095A 2" 9095A 3" |
||||||
OPW71SO |
OPW MODEL 71SO OVERFILL VALVE ASS'Y — •Mechanical two stage, positive shutoff overfill prevention valve.drop tube ass'y. •Available for direct bury and remote fill applications. The only vapor-tight overfill valve in the industry not requiring epoxy sealants. •Three variations for tank diameters to 12': –Model 71SO-400C for 8' diameter tanks (60" upper tube length, 155.75" overall length). –Model 71SO-410C for 10' diameter tanks (120" upper, 234.75" overall). –Model 71SO-720C for 12' diameter tanks (120" upper, 258.75" overall). |
MODEL OPW71SO-400C OPW71SO-410C OPW71SO-420C Parts OPW71SO-TOOL OPW61JSK-44CB OPW61JSK-4410 OPW61JSK-4RMT OPW61SOK-001 OPWH11931M OPWH14840M |
DESCRIPTION |
DOCS Features Install/Ops |
||||||
©2009 Mascott Equipment Co |